VRLA Battery for Grid/Hybrid Renewable Energy Storage
  • Part Number: 200GH
  • Product Line: Batteries
  • Related Categories: Store The Energy
EnergyCell GH

Product Highlights

  • Valve regulated lead acid battery
  • Designed for Grid/Hybrid renewable energy storage applications
  • Front terminal access for ease of installation and design
  • 18-month shelf life at 25˚C
  • EnerSys SBS EON technology gives higher energy density
  • Description

    The EnergyCell GH Valve Regulated Lead Acid (VRLA) battery is designed for Grid/Hybrid storage applications. EnerSys SBS EON technology incorporates TPPL AGM (Thin Plate Pure Lead Advanced Glass Mat) which allows for greater shelf life, extended float service life in optimal operating conditions, and higher energy density. The EnergyCell GH also features front terminal access with threaded copper inserts providing low maintenance and increased safety.


    Technical Specifications


    • Specifications

      EnergyCell GH Front Terminal Battery

        EnergyCell 200GH
      Cells Per Unit 6
      Voltage Per Unit 12 Vdc
      Operating Temperature Range (with temperature compensation) -40°F to 122°F (-40°C to 71°C)
      Optimal Operating Temperature Range 68°F (20°C) 
      Float Charging Voltage 13.62 Vdc/unit Average at 77°F (25°C)
      Equalization and Cycle
      Service Charging Limits
      14.4 Vdc/unit Average at 77°F (25°C)
      Self Discharge Battery can be stored up to 18 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.
      Temperature Compensation Factor
      (Charging)
      +/- 4mV per degree C per cell (2V)
      Terminal Threaded copper alloy insert terminal to accept ¼-20 UNC bolt
      Terminal Hardware Initial Torque M6 = 80 in-lbs (9.0 Nm)
      Weight (lbs/kg) 116 lbs (53 kg)
      Dimensions 11.1 x 22.1 x 4.9” (28.2 x 56.1 x 12.4 cm)